VFD
Beginner
Read Motor Nameplate and Set VFD
Motor ki nameplate se voltage, current, frequency, RPM padhna aur VFD ke basic parameters mein sahi se enter karna.
Given a motor nameplate image, identify rated voltage, current, frequency, RPM, and correctly enter these into VFD basic parameters.
Steps
- Read motor nameplate: voltage, current (FLC), frequency, RPM, power (kW/HP)
- Open VFD parameter menu (usually Group 0 or P0xx)
- Set motor rated voltage = nameplate voltage
- Set motor rated current = nameplate FLC
- Set base frequency = nameplate frequency (50 Hz in India)
- Save and verify — run motor at no load, check current draw
Common Mistake: Setting VFD rated current instead of motor nameplate FLC. Confusing supply voltage with motor voltage.
⚠ Ensure VFD is powered off before wiring. Lock-out tag-out before opening motor terminal box.